Starter Wye Delta 800HP 480V NEMA 1A
Starter Wye Delta Open Transition Enclosed Controller
Main Breaker 1200 Amp Frame with 1200 Amp Trip 65kAIC at 480 Volts 35kAic at 600 Volts
“100% Rated Breaker”
NEMA 1A Gasketed Doors
Enclosure Size: 84″x56″x19″
Mounting: Floor Mount
1124 Amp Max
Incoming Line Cable Lugs (4) 4/0-500MCM per phase
Outgoing Load Cable Lugs (2) 2-600MCM per (6) Motor Leads
Control Power Transformer 500VA with Primary and Secondary Short Circuit Protection
Control Relay DPDT 120V Coil
Timer On-Delay .6-60 Sec
Emergency Stop Pushbutton on Door
Motor Running LED Pilot Light
Overload Fault Indication LED Pilot Light
600:5 Current Transformer for Overload Relay
800 HP 480VAC MAX 1011 Service Factor Amps at 1.15
Overload Setting 4.89 800HP 480V
Field Wiring Line Side Required per Phase
(4) 4/0-500MCM
Wire Bending Space Required
16″ Line and Load